TYPE KX - PFA INSULATED CABLE

Siccet Siccet
TYPE KX - PFA INSULATED CABLE


DESCRIPTION
PFA insulation - overall screen - PFA jacket (IEC colour code)

APPLICATION
Temperature up to 260 °C and/or in aggressive chemical environment

CONSTRUCTION
- Reference standard: IEC 60584
- Conductor: solid or stranded
- Insulation: PFA
- Core laying-up: twisted conductors
- Extra layer: polyester tape
- Screen: aluminium/polyester bonded tape with tinplated copper drain wire
- Outer jacket: PFA
- Armour: stainless steel 304 braid
- Working temperature: -200/+260 °C
- Insulation resistance: > 20 Mohm x km (measured at 1000 Volt dc @ 20 °C)

ALTERNATIVE VERSION
- ASTM E230 (ANSI MC96.1-1982)
- DIN 43714
- BS 1843
- NFC 42324
- JIS C 1610-1981

Applications

Customized solutions to meet every specific need

Show allarrow down
Oil and Gas

Oil and Gas

Metal working industry

Metal working industry

Energy

Energy

Aerospace industry

Aerospace industry

Food industry

Food industry

Chemical and pharmaceutical industries

Chemical and pharmaceutical industries

Materials

High-quality materials for superior performance

Our cables are characterized by insulating materials and sheaths that provide unique properties. These high-quality materials offer tailored performance for each application requirement.

Show allarrow down